GXS Series Waste Water Level Transmitter

0-5 ftwc through 0-100 psi

Clog-free in Waste Water/Sludge/Slurry Applications

Designed for clog free operation

Dylix’s GXS submersible pressure transmitter is designed for OEM and end-users where continuous submersion in waste/sludge applications is required. The GXS’s key feature is its clog free design of the sensing diaphragm. This improves reliability and reduces down time, which lowers maintenance cost.

Manufactured for reliability in harsh well environments

The GXS is manufactured to perform overtime in harsh well environments. An internal network of MOV’s and dual gas discharge tubes protect against lightning, while triple sealing techniques ensure the integrity of the waterproof seal. This in turn results in fewer failures due to leakage. 100% of Dylix’s GXS transmitters are submerged at our factory for at least 24 hours.

Better Performance

Standard accuracy of .25%, lower thermal effects of 1.5% and less orientation sensitivity, resulting in more accurate readings.

Dylix’s Customer Service

Every GXS Series is shipped with a NIST traceable calibration certificate. Customer cable lengths or alternate wetted materials available.

Standard Features:

  • Moisture Free/Maintenance Free Vent Filter
  • Flush, clog-free sensor
  • Internal protection from lightning
  • EMI/RFI filters
  • Vent tube filter
  • 40 foot vented cable
  • ≤± 0.25% FSO Static Accuracy
  • NIST Certification

Available Options:

  • Tefzel® Cable
  • Low Power Consumption
  • Intrinsically Safe

Product Specifications

Electrical

Excitation 8-38 Vdc*
Output
GXS2 0-5 Vdc*
GXS3 4-20 mAdc
Zero Balance ≤±1% FSO
FSO Setting ≤±1% FSO
Resolution Infinite (±0.001% FSO usable)
Response Time < 5 mS
Insulation Resistance 1,000 M Ω @ 50 Vdc
Reverse Polarity Protected
Warm-up < 10 mS
Power Supply Effect ≤± 0.002% FSO per V input
EMY/RFI Internal Filtering
Lightening Protected MOV & dual gas discharge tube
Short Circuit Protected Up to 40 Vdc

* Options Available

Mechanical

Pressure Ranges 0-5 ftwc through 0-100 psi
(Customer may specify any range/eng. unit)
Proof Pressure 2X Full Scale*
Burst Pressure 5X Full Scale*
Materials 316L SST plus cable*
Pressure Port Flush mount per outline below*
Electrical Connector 1/2” NPT Male submersible conduit fitting with 40 feet of vented polyurethane cable*
Dimensions Per outline below
Weight Nominal 4 lbs.

Environmental

Compensated Temp Range 20 to 170º F
Operating Temp Range 0 to 200º F
Storage Temp Range -20 to 250º F

Performance

Static Accuracy ≤± 0.25% FSO* (BFSL, RSS)*
(Combined effects of non-linearity, hysteresis & repeatability)
Repeatability ≤± 0.1% FSO
Temperature Effects ≤± 1.5% FSO over comp range*
(Combined effects of Zero & FSO with reference at 70º F)
Long Term Stability ≤± 0.25% FSO per year

Standard Wiring

Model Output + Power - Power + Signal - Signal
GXS2 0-5 (10) Vdc 3 wire Red/Pin 1/Pin A Black/Pin 2/Pin B Green/Pin 3/Pin C
GXS3 4-20 mAdc 2 wire Red/Pin 1/Pin A
Black/Pin 2/Pin B

**Dylix Corporation reserves the right to change specifications without prior notification. Please contact the factory for the latest revision.